REQUEST QUOTE VIEW DATASHEET

Ark•Gard® ENR Premier Series (M4) Explosionproof Receptacles
ENR (M4) Receptacles are used:

In applications that require additional environmental protection

In areas made hazardous by the presence of flammable vapors and gases or combustible dusts

With portable or fixed electrical equipment such as motor generator units, welders, pumps, compressors, heating and cooling units, cellular relay stations, conveyors, lighting systems, and similar equipment

When power requirements do not exceed 20 amperes

FEATURES


Ark•Gard® 2 receptacle incorporates three spring-loaded slide keys that prevent the receptacle face plate from being rotated until the ENP plug is fully inserted into the receptacle; to make the connection, the ENP plug is fully inserted, and the receptacle face moved inward by pushing the plug forward; the plug is then rotated, closing the circuit; as rotation begins, the plug becomes locked in the receptacle and cannot be accidentally disengaged; in making or breaking the circuit, any resulting electrical arc is confined in the factory sealed chamber

Factory sealed chamber encloses the potential arcing components between two explosionproof threaded joints; these threads are specially coated to guarantee freedom of movement, which ensures on-off action; no additional seals are required

Gasketed screw cap cover design offers superior protection from harsh environments for increased product life

Protected hinged cover design provides 360° protection around cover hinge to reduce damage from dirt and corrosion

Saddle clamp terminals reduce installation and maintenance costs with easy to wire, time-saving terminals

Lockout/tagout hole complies with OSHA lockout/tagout requirements

CERTIFICATIONS
NEC:
Class I, Division 1, Groups B*, C, D
Class II, Groups F, G
Class III
NEMA 3, 3R

CEC‡:
Class I, Division 1, Groups B*, C, D
Class II, Group G
Class III
NEMA 3, 3R